SERIES A900MURPHYMATIC®GENERATORENGINE CONTROL SYSTEMDESIGN, INSTALLATIONAND OPERATING MANUALA900-9025NRevised 10-99Section 40(00-02-0197)

Strany 2 - MURPHY PRODUCT

7to operate a local audible alarm as required by NFPA- 110,Level 1 and Level 2.3-3.2.5 Remote Audible Alarm Relay; provides a contactclosure to oper

Strany 3 - Table of Contents

8setting until the overspeed trips. When switch isreleased, the set point will be 10% above normalrunning speed. This is the method used to make the

Strany 4 - Section 2: Specifications

9(c) TEST; turns on the engine controls and shutdown circuits.A start signal is applied to the automatic control and theengine start sequence begins.

Strany 5 - Figure 3-2.1

of cause of alarm. These circuits activate the alarm relay.Alarm circuits are active as long as power is applied to the A902-2. All are active when

Strany 6 - Table 3-1.7

3-6.1.2 Lamp Test Pushbutton: Tests the lights on the A903module.3-6.1.3 Alarm Silence Pushbutton: Turns off any audible alarmthat is connected to

Strany 7 - Figure 3-2.2

(h) #8 Spare Alarm; operated by an external switch. Thiscircuit is provided for an additional alarm that may berequired by the user.(i) #9 Spare A

Strany 8 - Figure 3-3.1

audible alarm will turn off when the alarm contact clears.3-7.1.4 The A903-2 SELECTRONIC®Control Module includesthe following engine control features

Strany 9 - Figure 3-3.2

make up the generator engine control. Relays are available foroperation on either 12 or 24 volt battery systems. Four (4)relays are included for:3-7

Strany 10 - Figure 3-4.1

5-1/2 in.(140 mm)3-3/4 in.(95 mm)3/16 in.(5 mm) dia.4 places5-5/8 in.(143 mm)2-13/16 in.(71 mm)3 in.(76 mm)3-3/8 in.(86 mm)6-3/4 in.(171 mm)9-3/8 in.(

Strany 11 - Figure 3-4.2

1526427284293031323334474849505152B+ OUTHOURMETERB- MANUAL STARTSTARTPICKUPPICKUPOIL PRESSURELO WATER TEMP.HI WATER TEMP.REMOTE S.D.SPARE ALARM3536373

Strany 12 - Figure 3-5.1

WARNINGBEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT✔ Disconnect all electricalpower to the machine.✔ Make sure the machine cannot operate duri

Strany 13 - Figure 3-5.2

Figure 4-2.3.2: A902 wiring1526427284293031323334B+ OUTHOURMETERB- MANUAL STARTSTARTPICKUPPICKUPOIL PRESSURELO WATER TEMP.HI WATER TEMP.REMOTE S.D.SPA

Strany 14

Figure 4-2.3.3: A903 wiring1526427284293031323334474849505152B+ OUTHOURMETERB- MANUAL STARTSTARTPICKUPPICKUPOIL PRESSURELO WATER TEMP.HI WATER TEMP.RE

Strany 15 - Figure 3-7.1

current rating that is equal to or greater than the forward currentthat the coil draws to operate. For example, a relay less than 1 A,use a 1 A diode

Strany 16

6. While engine is cranking, turn crank disconnectadjustment counter clockwise slowly until “CrankDisconnect Speed” light turns on and cranking stops.

Strany 17 - Figure 3-7.2

(c) “Water Temperature” light will come on and engine willstop.(d) Turn Mode Selector switch OFF.4-4.9 Low Water Temperature; to test the low water t

Strany 18 - Relay Module

Table 7-2.122ModeSelectorOFFMode SelectorAUTOStand-byMode SelectorAUTOCrankingMode SelectorAUTORunningMode SelectorAUTOShutdownInputVoltageInputVoltag

Strany 19 - Figure 4-2.3.1: A901 wiring

to the table for examples.(c) Voltages less than battery also may vary due to tolerancesof the electronic components in the A900. Minorvariations, 1

Strany 20 - Figure 4-2.3.2: A902 wiring

local audible (K-4) terminal 20 and 21, remote audible (K-5)terminal 22 and 23 and remote visual (K- 6) terminal 24 and 25close to operate the alarm d

Strany 21 - Figure 4-2.3.3: A903 wiring

0690040CONTROL SYSTEMS & SERVICES DIVISIONP.O. Box 1819; Rosenberg, Texas 77471; USA(281) 342-0297 fax (281) 341-6006 e-mail [email protected]

Strany 22 - Table 4-4.1

Table of ContentsSection 1: Introduction page 11-1 System 11-2 Models 11-3 Purpose 11-4 Definitions 11-5 How To Use This Manual 1Section 2: Specificat

Strany 23 - Figure 4-4.1.3

Section 1: Introduction1-1 System.1-1.1 The MURPHYMATIC®Generator Engine Control System,Series A900 is designed to meet the requirements of the engin

Strany 24 - Section 5: Operation

an automatic-start, two-cycle, engine-driven generator, andinclude the shutdown and alarm points recommended in NFPA-110-1988 “Emergency and Standby G

Strany 25 - Table 7-2.1

Table 3-1.73Level 1C.V.SL.A.R.A.R.V.Level 2C.V.SL.A.R.A.R.V.NFPA-110NFPA99C.V.SL.A.R.A.R.V.②CAN/CSAC282-M89C.V. S L.A. R.A. R.V.A901C.V.S L.A. R.A. R.

Strany 26

(d) Overcrank circuit; will stop automatic cranking andindicate overcrank if engine fails to start after 3 attempts.The number of cranks are selectab

Strany 27 - Section 8: Service Parts

energize the battery charging alternator field.3-2.2.2 Shutdown Relay; this relay is operated by the shutdowncircuits of the Control / Display Modul

Strany 28 - FWMurphy

(f) Overspeed Speed Switch;1. Provides a signal to the overspeed shutdown circuit ifthe engine exceeds the preset speed. The factorysetting is appro