If switch trip point needs to be adjusted, see page 4.
LLS Series Hook-up (all models)
To wire the LLS Series, use proper the electrical conduit.
1. A 3/4''-14 NPT inlet connection for conduit installation is provided
at the top end of the switch enclosure (see opposite page–
“Dimensions” for location).
NOTE: The plastic plug (supplied) is to protect the conduit inlet threads
and must be removed before wiring the unit.
2. Using a 3/16 in. hex wrench, unscrew the 4 hex-cap screws.
Now proceed to remove the square cover to reveal snap-switch(es).
3. To wire the unit, refer to the typical wiring drawing (Figure 3) and
to the Schematic (shown at right). Wire the LLS Series switch(es)
with 60°/75°C (140°/167°F) insulated wire.
4. A terminal (inside the switch enclosure) is provided for case or
equipment grounding, refer to Figure 3 for location.
5. After completing wiring, replace the switch cover and make sure it
is tightly secured before applying power to the system.
3
WIRING THE LLS SERIES PRESSURE SWITCH
Provision for
Case Ground
N.O. N.C. COM.
Terminal
Block(s)
Customer
Wiring
NC NO C NC NO C
3/4 in.-14 NPT
Conduit Inlet
WARNING: PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF”. MAKE SURE VOLTAGE AND CURRENT REQUIRE-
MENTS ARE WITHIN THE LLS RATINGS. BEFORE WIRING THE UNIT DETERMINE VOLTAGE AND POLARITY FOR THE APPLICATION.
IF THE UNIT IS USED IN HAZARDOUS AREAS, MAKE THE AREA SAFE BEFORE REMOVING THE SNAP-SWITCH(ES) COVER.
Figure 3
SPDT
DPDT
NC
C
NO
P
NC
C
NO
P
NC
C
NO
Schematic
INSTALLING THE LLS SERIES PRESSURE SWITCH
Connecting the LLS and LLSB Series
To install the LLS and LLSB Series,
a vertical mounting is recommended.
1. The unit threads directly into a 2 in. 11-1/2 NPT tee on the lead line.
2. Tighten the bottom housing to the lead line tee using ONLY the
transmitter wrench flats (see figure 1).
3. Check for leakage on any of the connections. Make sure that the
installation conforms with local and other applicable codes.
Connecting the LLSR and LLSRB Series
For mounting the switch enclosure refer to “Dimensions” on page 2.
The following instructions are based on the usage of a PD8187 Pulsation
Dampener option shown in Figure 2 (at right.)
1. Install sensor/pulsation dampener into pressure source connection.
2. Loosen the eight housing bolts until the bottom housing is free to turn.
3. Tighten the bottom housing to the pulsation dampener connection.
4. Tighten the eight housing bolts to 25±3 foot lbs. Stagger the tighten-
ing to assure even clamping.
5. Route capillary away from heat source (exhaust manifold). Excess
capillary should be carefully coiled and secured (do NOT cut it).
2 in. NPT
Use Wrech Flats to
Screw the LLS
Into the Process
Do NOT Tamper with
This Connection
Do NOT Tamper with
these Sealed Connections
Lead line tee
Wrench Flats
WARNING: PERFORM THE INSTALLATION WITH POWER SOURCE “OFF”. NEVER EXCEED RATED PRESSURE RANGE FOR THE UNIT.
USE WRENCH ON SHANK TO TIGHTEN/LOOSEN CONNECTIONS. DO NOT TWIST THE ENCLOSURE WHEN SCREWING THE LLS INTO THE
PROCESS – THIS WILL DAMAGE INTERNAL COMPONENTS, FILLED MECHANISM AND THE SEALS. DO NOT OVERTIGHTEN THE UNIT.
CAUTION: THE PD8187 PULSATION DAMPENER IS NOT INTENDED
AS A SHUTOFF VALVE. APPLY PIPE SEALANT TO THE THREADS.
CAUTION: DO NOT TAMPER WITH OR BREAK SEALED CONNEC-
TIONS. APPLY PIPE SEALANT TO PROCESS CONNECTION THREADS.
CAUTION: WHEN LOOSING THE EIGHT HOUSING BOLTS, MAKE
SURE NOT TO UNSCREW THE GREEN DIAPHRAGM CAPSULE.
Transmitting Tubing
(capillary)
Housing
Bolts
Diaphragm
Body
Pulsation
Dampener
(optional)
Wrench
Flats
Lead Line Tee
1 in. NPT
Figure 1
Figure 2
SPDT DPDT
Zobrazit stránku 2
1 2 3 4

Komentáře k této Příručce

Žádné komentáře

HP Omni Pro 110 Business PC manuali

Manuali dei proprietari e guide per l'utente per Tavolini per PC/Workstation HP Omni Pro 110 Business PC.
We fornisce 1 manuali pdf HP Omni Pro 110 Business PC per scaricare gratuitamente in base al tipo di documento: Specifiche


Hp Omni Pro 110 Business PC Specifiche (93 pagine)


Marchio: Hp | Categoria: PC/workstation barebones | Dimensione: 4.38 MB |

 




Più prodotti e manuali per Tavolini per PC/Workstation HP

Modelli Tipo di Documento
100B - All-in-One PC Informazioni Techniche   HP 100B - All-in-One PC System information, 104 pagine
Vectra VL400 Manuale Utente   5 HP Vectra VL400 SFF PC, 10 pagine
9020 CE Manuale di Servizio   HP 9020 CE Technical data, 186 pagine
Compaq t5125 Manuale Utente   HP Compaq t5125 Thin Client - Hewlett, 2 pagine
Compaq dc7500 MT Manuale Utente   HP Compaq dx7500 Business PC, 52 pagine
Compaq Presario,Presario 6007 Manuale Utente   1 ARLINGTON COUNTY POLICE DEPARTMENT 1425 NORTH, 4 pagine
EliteOne 800 Manuale Utente   HP EliteOne 800 G1 All-in-One Business PC Impressive, 4 pagine
IQ524 - TouchSmart - 4 GB RAM Manuale Utente   Upgrading and Servicing Guide HP Touchsmart PC, 26 pagine
Deskpro EX C600 Manuale Utente   Trip report, Cook Islands, Wed 18 March - Wed 9 April [en] [es] , 42 pagine
z545 Manuale Utente   HP z545-b Digital Entertainment Center, 5 pagine
t5630 Thin Client Guida Utente   HP t5630 Thin Client Hardware reference guide, 39 pagine
5900 Manuale Utente   HP 5900 switch - Enet Configuration Guide, 5 pagine
Kayak XW U3-W3 Manuale Utente   BIOS beep codes list for desktops, 7 pagine
Pavilion 304 Manuale Utente   Technische Details, 2 pagine
XW8200 Manuale Utente   HP xw8200, 5 pagine
Compaq Presario,Presario 5010 Specifiche   HP Compaq Presario,Presario 5010 Specifications, 216 pagine
Blade bc1000 Manuale Utente   Storage Architectures for Server Blade Environments, 35 pagine
Elite 7300 Microtower PC Manuale Utente   HP Elite 7300 Microtower PC User manual, 4 pagine
8000 - Elite Convertible Minitower PC Guida Utente   HP 8000 - Elite Convertible Minitower PC Hardware reference guide, 64 pagine
Z230 SFF Workstation Manuale Utente   HP Z230 Tower and SFF Workstations, 4 pagine